Operating Concept: It is an electromechanical (motorized) valve that isnormally closed. It opens when energized and uses a powerful internal spring to close in less than one second when the electrical signal is removed.
Pressure Rating: Typically rated for a maximum operating pressure differential (MOPD) of50 PSIG(3.45 bar).
Materials: Standard construction includes acast iron body(though steel and stainless options exist), 400 series stainless steel seat, andBuna-N O-rings.
Voltage: Standard configurations operate on115VAC/60 Hz.
Integrated Controls: Often paired withVCS-VOS(Visual Position Switches) for proof-of-open and proof-of-closure monitoring